Fiche technique du produit - MZSVB4-12
Extrémité thermorétract. de câble,moyenne tension,intérieur
3×1×185-300mm2, 12kV
Code d'article:MZSVB4-12
(EAN: 5997374108966)
3×1×185-300mm2, 12kV
Extrémité thermorétract. de câble,moyenne tension,intérieur
Code d'article:MZSVB4-12 (EAN: 5997374108966)Caractéristiques techniques 3×1×185-300mm2, 12kV
1 pc(s) en stock
Extra discount: 5,00 %
HT
110,36842 EUR 104,85000 EUR
110,36842 EUR 104,85000 EUR
TTC
140,16789 EUR
133,15950 EUR
type:
autre
adapté à:
autre
Garantie:
2 année
Heat shrinkable, indoor terminal kits for single-core, XLPE insulated, wire or tape screened cables (e.g. N2XSY, 2XSY, NA2XSY, A2XSY, NA2XS2Y, A2XS2Y types) with aluminum or copper conductor, without connectors. The kit contains three, single core terminals.
The kit contains one, single-core termination.
Tracon code
|
Size (mm2)
|
Max. voltage (kV)
|
Cable cross-section (mm2) |
Length of terminat. (mm)
|
MZSVB4-12
|
3×(1)×185-300
|
12
|
185-300
|
350
|
|
|
||||
Sealing of the (C) and (D) layers of the medium voltage cable (B) is made by using stress control tape (2) and stress control tube (3). Possible gaps on the cable lug (1) are eliminated by using filling mastics (4).
Cable screening (E) elements: In case of wire screening: PVC tape (6), shielded earth-connection lug (10). In case of tape screening: adhesive copper tape (7), tinned copper mesh (8), constant force spring (9). The termination is protected against weathering, UV radiation and mechanical effects by antitrack tube (5), shrunk onto the outer jacket (F). |
The proper copper or aluminum lugs (1) (no part of the kit) should be selected based upon the cross section of the cable core (A).